Jiangsu Yawei Transformer Co., Ltd.

1250 kva Pad Mounted Transformer

Power Rating: 1250 kVA

Primary Voltage Ratings: 34.5-19.92/13.8-7.957/13.2-7.62/12.47-7.2,11,12.47 or others

Secondary Voltage Ratings: 208GrdY/120;416GrdY/240,480GrdY/277,/600GrdY/347,220y/127,480V,415v,600v or others

H.V. TAP RANGE: ±2×2.5% or others

Winding connection: Dyn11/YNyn0 or others

TYPE: Loop feed/Radial feed

BIL: 30-150kV

Standards: ANSI, CSA, NEMA, IEEE, DOE, etc

Certificates:ISO,UL

 

Product Introduction

 

Pad-mounted transformers are made in power ratings from around 75 toaround 5000 kVA and often include built-in fuses andswitches.Primary power cables are connected with elbow connectors.which can be operated when energized using a hot stick andallows for flexibility in repair and maintenance.Our pad mounted transformer is designed and tested in accordance withindustry standards including CSA,ANSI C 57,DOE,and lEEE as applicable.

 

page-800-600
page-800-600
Technical Specification

 

Pad Mounted Transformer

Rated Capacity (KVA)

High Voltage(KV)

Low Volatge(V)

Loss(W)

No Load Loss (W)

On Load loss (W)

75KVA

34.5KV/

19.92KV/

13.8KV/

79.57KV/

13.2KV/

7.62KV/

12.47KV/

7.2KV

or others

240V

480V

480Y/

277V

600Y/

347V

180

1250

112.5KVA

200

1500

150KVA

280

2200

225KVA

400

3050

300KVA

480

3650

500KVA

680

5100

750KVA

980

7500

1000KVA

1150

10300

1500KVA

1640

14500

2000KVA

2160

20645

2500KVA

2680

27786

3000KVa

3300

30300

3750KVA

4125

37875

 

page-1200-1537

Tests

 

Each transformer receives all standard commercial tests in accordance with ANSI C57.12.90 (latest revision), with test reports available by serial number of the transformer.

• Resistance tests of all windings.

• Ratio tests on the rated voltage and all tap connections.

• Polarity and phase relation tests at rated voltage.

• No load loss at rated voltage.

• Exciting current at rated voltage.

• Impedance and load losses.

• Applied voltage test.

• Induced voltage test.

• Full-wave impulse test.

• Mechanical leak test.

 

Quality Standards Of Product

 

product-1000-700

1.Quality management system GB/T 19001-2016 ISO 9001: 2015

The operation of the whole YAWEI system is strictly controlled and managed. This ensures the quality of products and material in all stages, from receiving customer requests to design, materials, production, installation, testing, packaging, delivery, after-sales, all of which operate under strict and logically linked processes.

2.CERTIFICATEOFCOMPLIANCE of UL and CUL

YaWei pad mounted transformer have been evaluated by UL in accordance with the U.S and Canada Standard(s). Our transformer certified by UL based on Canadian standards (CSA standards) .

3.Accreditation certificate CE

Standard: EN 60076-1:2011.EN 60076-2:2011EN 60076-14:2013 confirms that YAWEI technical quality meets the requirements of all specific international standards for testing and calibration laboratories. All YAWEI products are fully tested in a qualified testing room before leaving the factory, ensuring stable quality and providing absolute peace of mind for customers.

 

Rated Capacity(kVA)

No-load Loss(kW)

Load Loss(kW)

No-load Current(%)

Impendance Voltage(%)

Dimension (LxWxH)

(mm)

Total Weight

(kg)

100

200

1500

0.65

4.0

1180x1355x1735

729

150

280

2200

0.60

 

1830x1375x1735

989

200

340

2600

0.50

 

1830x1375x1735

1195

250

400

3050

0.50

 

1830x1405x1735

1355

315

480

3650

0.45

 

1830x1425x1735

1415

400

570

4300

0.45

 

1830x1435x1805

1675

500

680

5150

0.40

 

1830x1445x1860

1905

630

810

6200

0.40

4.5

1830x1445x1860

2165

800

980

7500

0.35

 

1830x1490x1860

2755

1000

1150

10300

0.35

 

1830x1675x2005

3235

1250

1360

12000

0.30

 

2100x1845x2035

4905

1600

1640

14500

0.30

 

2100x1885x2135

5835

 

Main Products Of YAWEI