Jiangsu Yawei Transformer Co., Ltd.

ZGS20-Z·G Combined Transformer for Photovoltaic Power Generation

Altitude not exceeding 3000 meters;
Ambient temperature range: -40°C to +45°C;
Outdoor wind speed not exceeding 30m/s;
Relative humidity: daily average not greater than 95%, monthly average not greater than 90%.
Installation location: should be free from the risk of fire, explosion, severe pollution, chemical corrosion, and intense vibrations.
The waveform of the power supply voltage should be approximately sinusoidal, and the three-phase power supply voltage should be approximately symmetrical. If the conditions exceed these normal operating environment conditions, users can consult with our factory to find a solution."

 

Product Introduction

 

product-1000-750

 

The ZGS20-Z·G Combined Transformer for Photovoltaic Power Generation is a specialized piece of equipment designed to meet the unique requirements of solar power systems. Here are some key points about its structure and features as described in the provided search results:

 

  1. Integration of Components: The transformer integrates several components such as step-up transformers, photovoltaic current-limiting fuses, load switches, and low-voltage switchgear along with corresponding auxiliary equipment.
  2. Voltage Step-Up: It is designed to step up the 315V (alternative options include 270V, 300V, 400V) voltage generated by the photovoltaic power generation group to 35KV, facilitating the transmission of electrical energy through a 35KV cable line.
  3. Structural Design: The box transformer is divided into four parts: the transformer body, high voltage room, low voltage room, and the fuse and switch operation room, which can be arranged in various configurations.
  4. Protection Features: The high-voltage side is equipped with a terminal load switch and a full-range current-limiting protection fuse for enhanced safety.
  5. Heat Dissipation: The load switch and fuse are installed in the transformer oil tank, using the transformer's insulating oil as both the insulating and heat dissipation medium, contributing to a compact structure with good thermal performance.
  6. Outlet Configuration: The high-voltage side outlet uses a dry-type bushing to support the copper busbar structure, allowing for the connection of multiple cables. The low-voltage side can be directly connected or configured according to user requirements.
  7. Sealing and Weather Resistance: The door of the box substation uses a windproof hinge with sealing measures and a door seal. The entire box body is sealed with no exposed or removable bolts, using concealed high-strength bolts and oil-resistant rubber gaskets for the cover.
  8. Durability: The cabinets are finished with baked paint, providing strong resistance to outdoor weather conditions.
  9. Corrosion Resistance: The transformer body is made of medium-thick steel plates, and the exterior is made of galvanized plates or stainless steel plates that have undergone acid washing, phosphating treatment, and coated with primer, intermediate paint, and top paint to ensure excellent corrosion resistance, leak prevention, and UV resistance.
  10. Ease of Installation: The combined transformer is compact, lightweight, and easy to install, making it suitable for a wide range of applications.

 

These features make the ZGS20-Z·G Combined Transformer an efficient and reliable choice for photovoltaic power generation systems, offering a robust solution for energy transmission and distribution in solar power projects.

 

Main Features of the Product

 

The main features of the ZGS20-Z·G Combined Transformer for Photovoltaic Power Generation include:

 

  1. Specialized Design: It is a dedicated electrical equipment developed for the unique requirements of photovoltaic power generation.
  2. Component Integration: The product integrates a step-up transformer, photovoltaic current-limiting fuses, load switches, low-voltage switchgear, and corresponding auxiliary equipment into a single unit.
  3. Efficient Voltage Step-Up: It is designed to step up the voltage from the photovoltaic power generation group to 35KV, allowing for efficient energy transmission through a 35KV cable line.
  4. Modular Structure: The transformer is divided into distinct sections including the transformer body, high voltage room, low voltage room, and the fuse and switch operation room, which can be arranged flexibly.
  5. Enhanced Safety: The high-voltage side is equipped with a terminal load switch and a full-range current-limiting protection fuse for added safety.
  6. Effective Heat Dissipation: The load switch and fuse are installed in the transformer oil tank, using the transformer's insulating oil for both insulation and heat dissipation, contributing to a compact structure with good thermal performance.
  7. Versatile Outlet Configuration: The high-voltage side outlet uses a dry-type bushing to support the copper busbar structure, facilitating the connection of multiple cables. The low-voltage side can be configured according to user requirements.
  8. Weather-Resistant Construction: The door of the box substation is designed with windproof hinges, sealing measures, and a door seal to ensure the equipment is protected from the elements.
  9. Robust Sealing: The box body is sealed with no exposed or removable bolts, using concealed high-strength bolts and oil-resistant rubber gaskets for the cover, ensuring a robust seal.
  10. Durable Finish: The cabinets are finished with baked paint, which provides strong resistance to outdoor weather conditions.
  11. Corrosion-Resistant Materials: The transformer body is made of medium-thick steel plates, and the exterior is made of galvanized plates or stainless steel plates that have undergone acid washing, phosphating treatment, and coated with primer, intermediate paint, and top paint for excellent corrosion resistance.
  12. Ease of Installation: The combined transformer is compact and lightweight, making it easy to install and suitable for a wide range of applications.

 

These features highlight the ZGS20-Z·G Combined Transformer as a reliable and efficient solution for photovoltaic power generation.

 

 

 

Item Unit Parameters

High Voltage Unit

Rated Voltage

KV

12

 

Power frequency withst arid voltage to ground, imer-phase, fracture witllin 1 min

KV

42/48

 

Lightning impu[se voltage ground, inter-phase, fracture

KV

75/85

 

Rated current

A

315-630

 

Rated short-itme withstand current (4s)

KA

2040

 

Rated peak withstand current

KA

50-100

Low Vohage Unit

Rated Vohage

V

≦690

 

Main bus-bar rated current

A

100-400()

 

Rated short-time withstand current (4s)

KA

25-75

 

Rated peak withstand current

KA

40-150

 

Compensation capacity

KVAR

customized

Transformer Unit

Rated Volta

KV

10

  Frequency HZ 50
 

Rated capacity

KVA

30-2500

 

Impedance voltage

%

416

 

Tapping range

/ +2*2.5%/+5%
 

Combination symbol

/ Dyn11/Yyn0

Protect case

Protection grade

IP33

 

page-1655-711

 

Quality Standards Of Product

 

product-1000-700

1.Quality management system GB/T 19001-2016 ISO 9001: 2015

The operation of the whole YAWEI system is strictly controlled and managed. This ensures the quality of products and material in all stages, from receiving customer requests to design, materials, production, installation, testing, packaging, delivery, after-sales, all of which operate under strict and logically linked processes.

2.CERTIFICATEOFCOMPLIANCE of UL and CUL

YaWei pad mounted transformer have been evaluated by UL in accordance with the U.S and Canada Standard(s). Our transformer certified by UL based on Canadian standards (CSA standards) .

3.Accreditation certificate CE

Standard: EN 60076-1:2011.EN 60076-2:2011EN 60076-14:2013 confirms that YAWEI technical quality meets the requirements of all specific international standards for testing and calibration laboratories. All YAWEI products are fully tested in a qualified testing room before leaving the factory, ensuring stable quality and providing absolute peace of mind for customers.

 

Winding on the primary and secondary windings has an excellent design structure to help the machine operate effectively.

Insulation wire wrapping line

Yawei three phase pad-mounted transformer oil tank casting workshop. Professional work and team for different mold requirements.

Yawei configuration fin/ radiator producing workshop.

 

Item

Unit

Parameters

High Voltage Unit

Rated Voltage

KV

12

 

Power frequency withstand voltage to ground, inter-phase, fracture within 1min

KV

42/48

 

Lightning impulse voltage ground, inter-phase, fracture

KV

75/85

 

Rated current

A

315-630

 

Rated short-time withstand current (4s)

KA

20-40

 

Rated peak withstand current

KA

50-100

Low Voltage Unit

Rated Voltage

V

≤690

 

Main bus-bar rated current

A

100-4000

 

Rated short-time withstand current (4s)

KA

25-75

 

Rated peak withstand current

KA

40-150

 

Compensation capacity

KVAR

Customized

Transformer Unit

Rated Voltage

KV

10

 

Frequency

Hz

50

 

Rated capacity

KVA

30-2500

 

Impedance voltage

%

4/6

 

Tapping range

-

±2*2.5%/±5%

 

Combination symbol

-

Dyn11/Yyn0

Protect case

Protection grade

IP33

 

Main Products Of YAWEI