As a supplier of 138kv/132kv power transformers, I understand the critical role these transformers play in the electrical grid. A 132kv power transformer is a complex piece of equipment that steps down high-voltage electricity for distribution to homes and businesses. When issues arise, prompt and accurate troubleshooting is essential to minimize downtime and prevent further damage. In this blog, I'll share some key steps and considerations for troubleshooting a 132kv power transformer.
Initial Checks
Before delving into more in - depth troubleshooting, it's important to perform some basic checks. First, visually inspect the transformer for any obvious signs of damage, such as oil leaks, cracked bushings, or physical deformities. An oil leak can be a serious issue as it not only indicates a potential structural problem but can also lead to a loss of insulation and cooling capacity.
Check the transformer's cooling system. Transformers are typically cooled by oil circulation, and any blockages in the cooling pipes or radiators can cause overheating. Ensure that the fans, if present, are working properly and that the oil level in the conservator tank is within the normal range.
Examine the transformer's protection relays. These relays are designed to detect abnormal conditions such as over - current, over - voltage, and earth faults. If a relay has tripped, it can provide valuable clues about the nature of the problem. Look at the relay's indication lights or check the event log to determine what triggered the trip.
Testing the Electrical Parameters
Once the initial visual checks are complete, it's time to test the electrical parameters of the transformer. One of the most fundamental tests is the measurement of the winding resistance. This test helps to identify any short - circuits or open - circuits in the windings. A significant deviation from the rated winding resistance can indicate a problem with the winding insulation or a broken conductor.
Use a megohmmeter to measure the insulation resistance between the windings and between the windings and the transformer tank. A low insulation resistance value may suggest moisture ingress, insulation degradation, or contamination. It's important to note that the insulation resistance measurement should be taken under stable temperature and humidity conditions for accurate results.
Another important test is the turns ratio test. This test verifies the ratio of the number of turns in the primary and secondary windings. A deviation from the rated turns ratio can indicate a fault in the winding, such as a short - circuited turn. The turns ratio test can be performed using a turns ratio tester, which applies a known voltage to the primary winding and measures the induced voltage in the secondary winding.
Analyzing the Oil
Transformer oil serves multiple purposes, including insulation and cooling. Analyzing the oil can provide valuable insights into the internal condition of the transformer. One of the common tests is the dissolved gas analysis (DGA). This test measures the concentration of various gases dissolved in the oil, such as hydrogen, methane, ethane, ethylene, and acetylene.
Different types of faults in the transformer can produce characteristic gases. For example, overheating can cause the decomposition of the oil and the formation of methane and ethylene. A high concentration of hydrogen may indicate partial discharges within the insulation. By analyzing the gas concentrations and their ratios, it's possible to identify the type and severity of the fault.
In addition to DGA, the oil's physical and chemical properties should also be tested. This includes measuring the oil's dielectric strength, water content, and acidity. A low dielectric strength can indicate contamination or degradation of the oil, while a high water content can reduce the insulation performance and increase the risk of electrical breakdown.
Dealing with Specific Faults
Overheating
If the transformer is overheating, first check the cooling system as mentioned earlier. If the cooling system is functioning properly, the overheating may be due to an internal fault, such as a short - circuited turn or excessive load. Reduce the load on the transformer if possible and monitor the temperature. If the overheating persists, further testing and inspection are required to identify and repair the internal fault.


Partial Discharges
Partial discharges are small electrical discharges that occur within the insulation. They can be detected through DGA and also by using partial discharge detectors. If partial discharges are detected, it's important to determine their location and severity. In some cases, the insulation may need to be dried or repaired, or the affected components may need to be replaced.
Earth Faults
An earth fault occurs when a conductor comes into contact with the earth or the transformer tank. This can be detected by the protection relays. To locate the earth fault, a fault locator can be used. Once the fault is located, the damaged conductor or insulation should be repaired.
Importance of Regular Maintenance
Regular maintenance is crucial for preventing problems in 132kv power transformers. This includes scheduled inspections, oil testing, and electrical parameter testing. By detecting potential issues early, it's possible to avoid costly breakdowns and extend the lifespan of the transformer.
As a supplier, we offer high - quality Oil Immersed Transformer that are designed to meet the highest industry standards. Our 125MVA 138KV 24.94KV Step Down Transformer is a reliable solution for power distribution networks. If you are interested in our Oil Immersed Transformer or have any questions about transformer troubleshooting, feel free to contact us for procurement and further discussion.
References
- "Power Transformer Engineering: Design, Technology, and Diagnostics" by G. C. Swarmy
- IEEE Standard C57.104 - Guide for the Interpretation of Gases Generated in Oil - Immersed Transformers
- IEC 60076 - 1: Power transformers - Part 1: General
