Temperature control system for dry-type transformers

Sep 30, 2022 Leave a message

The safe operation and service life of dry-type transformers largely depend on the safety and reliability of the insulation of the transformer windings. The winding temperature exceeding the insulation tolerance temperature causes insulation damage, which is one of the main reasons why transformers cannot work normally. Therefore, monitoring and alarm control of the operating temperature of transformers is very important.
⑴ Automatic control of the fan: The temperature signal is measured by a Pt100 thermistor embedded in the hottest part of the low-voltage winding. The transformer load increases and the operating temperature rises. When the winding temperature reaches 110 ℃, the system automatically starts the fan for cooling; When the winding temperature drops to 90 ℃, the system automatically stops the fan.
⑵ Overtemperature alarm and trip: The temperature signal of the winding or iron core is collected through the PTC nonlinear thermistor embedded in the low-voltage winding. When the temperature of the transformer winding continues to rise and reaches 155 ℃, the system outputs an over temperature alarm signal; If the temperature continues to rise to 170 ℃, the transformer can no longer operate and an over temperature trip signal must be sent to the secondary protection circuit to quickly trip the transformer.
⑶ Temperature display system: The temperature change value is measured by a Pt100 thermistor embedded in the low-voltage winding, and the temperature of each phase winding is directly displayed (three-phase inspection and maximum value display, and historical highest temperature can be recorded). The highest temperature can be output as a 4-20mA analog quantity, and if needed, it can be transmitted to a remote computer (up to 1200m away)